Features
-
DC Parameters
-
AC parameters (On-Grid)
-
AC parameters (Off-Grid)
-
Transformer
-
General data
-
Features
-
DC Parameters
-
AC parameters (On-Grid)
-
AC parameters (Off-Grid)
-
Transformer
-
General data
Technical Specs
-
· PCS Max. efficiency up to 99%
· Full reactive power four-quadrant capability
· Support VSG function
· Millisecond-level power response to EMS/SCADA -
· NEMA TYPE 3R protection
· Black start ability
· Four or two DC branch inputs
· Integrated MV transformer and LV auxiliary power supply
Model | EH-5000-HB-UD-US-34.5 |
---|---|
Max. DC voltage | 1500V |
Max. DC current | 5612A |
Battery voltage range | 1000~1500V |
Number of DC input | 4 or 2 |
Model | EH-5000-HB-UD-US-34.5 |
---|---|
AC Output power | 5500kVA@30℃, 5000kVA@45℃ |
PCS Nominal AC Voltage | 690V,3W+PE |
PCS AC voltage range | 607~759V (Adjustable) |
PCS Max. AC current | 4604A@30℃,4184A@45℃ |
Nominal grid frequency | 60Hz |
Harmonic (THDi) | <1.5% (100% load) |
Power Factor | -1~+1 |
Model | EH-5000-HB-UD-US-34.5 |
---|---|
PCS Nominal AC voltage | 690V,3W+PE |
PCS AC voltage range | 607-759V(Adjustable) |
AC voltage distortion | <1.5% (100% linear load) |
DC voltage component | <0.5% Un (Linear balance load) |
Unbalanced load capacity | 100% |
Nominal grid frequency | 60Hz |
Model | EH-5000-HB-UD-US-34.5 |
---|---|
Isolation mode | Oil-Immersed Transformer |
Transformer rated power | 5500kVA@30℃,5000kVA@45℃ |
LV/MV voltage | 0.69kV/34.5kV (10kV~34.5kV Optional) |
Transformer vector | Dy1 or Dy11 |
Transformer cooling type | KNAN |
Oil type | Degradable oil |
Model | EH-5000-HB-UD-US-34.5 |
---|---|
PCS Max. efficiency | 98.9% |
PCS CEC efficiency | 98.5% |
Ingress protection rating | TYPE 3R |
Operating temperature range | -40~+60℃(>45℃ derating) |
Relative humidity | 0~100% (no condensing) |
Max. altitude | 1000m |
Cooling method | Forced air cooling |
Communication port | RS485/CAN/Ethernet/Bluetooth |
Dimensions (W*D*H) | 6058×2438×2896mm |
Weight | 20000kg |