Central Power Conversion System

EH-1725-HA-UD-US

Power Conversion System (Central PCS, 1500V)

  • 2MW PCS (1).png
  • 2MW PCS (2).png
  • 2MW PCS (3).png
  • 2MW PCS (1).png
  • 2MW PCS (2).png
  • 2MW PCS (3).png
  • Features

  • DC Parameters

  • AC parameters (On-Grid)

  • AC parameters (Off-Grid)

  • General data

  • Features

  • DC Parameters

  • AC parameters (On-Grid)

  • AC parameters (Off-Grid)

  • General data

Features
  • · Max. efficiency up to 98.9%
    · Full reactive power four-quadrant capability
    · Support VSG function
    · Millisecond-level Power response to EMS/SCADA

  • · NEMA TYPE 3R protection degree
    · Black start ability
    · Three level topology
    · Use alone or in combination with MV station

DC Parameters
ModelEH-1725-HA-UD-US
Max. DC voltage1500V
Max. DC current1936A
Battery voltage range1000~1500V
Number of DC input1
AC parameters (On-Grid)
ModelEH-1725-HA-UD-US
AC output power1897.5kVA@30℃, 1725kVA@45℃
Nominal AC voltage690V, 3W+PE
AC voltage range607~759V (Adjustable)
Max. AC output current1588A@30℃, 1443A@45℃
Nominal grid freqency60Hz
Harmonic (THDi)<1.5% (100% load)
Power factor range-1~+1
AC parameters (Off-Grid)
ModelEH-1725-HA-UD-US
Nominal AC voltage690V,3W+PE
AC voltage range607-759V(Adjustable)
AC voltage distortion<1.5% (100% linear balance load)
DC voltage component<0.5% Un (Linear balance load)
Unbalanced load capacity100%
Nominal grid frequency60Hz
General data
ModelEH-1725-HA-UD-US
Isolation modeTransformerless
Max. efficiency98.90%
CEC efficiency98.50%
Ingress protection ratingTYPE 3R
Operating temperature range-40~+60℃ (>45℃ derating)
Relative humidity0~100% (no condensing)
Max. altitude5000m (>3000m derating)
Cooling methodForced air cooling

Communication port

RS485/CAN/Ethernet/Bluetooth
Dimensions (W*D*H)1150×1435×2350mm
Weight1400kg